ECE 307 HW# 5 for WEDS 3/26/25
[Gruss probs 5.2, 5.11, 5.13]
5.2. A four-winding ideal transformer has windings with the following numbers of
turns: $N_1$ = 1000 turns, $N_2$ = 500 turns, $N_3$ = 2000 turns, $N_4$ = 3000 turns.
The windings are terminated as follows:
1. Source $V_1$ = 1000/0° V.
2. impedance $Z_2$ = 10 $\Omega$
3. impedance $Z_3$ = 40 - j30 $\Omega$
4. impedance $Z_4$ = j100 $\Omega$
(a) Draw a circuit diagram, defining all winding currents and voltages.
(b) Solve for all winding currents and voltages.
(c) Calculate the complex power into winding 1.
(d) Calculate the complex power out of winding 2.
(e) Calculate the complex power out of winding 3.
(f) Calculate the complex power out of winding 4.
(g) Does the complex power of (c) equal the summation of that calculated in
(d), (e), and (f)? Should it?
5.11. Consider the 3$\phi$ system as shown
Y $\Delta$
Bank T1
3 - 1$\phi$ 35 MVA
138 kV:34.5 kV
Z = 1 + j7.5%
on ratings
$\Delta$ Y
Bank T2
1 - 3$\phi$ 90 MVA
35 kVA:7.2 kVY
Z = 1 + j6%
on ratings
$\frac{Z = 5 + j20 \Omega}{Y/2 = j0.10 mS}$
(a) Tabulate all four base values ($S_{base}$, $V_{base}$, $I_{base}$, $Z_{base}$) at all four buses (16
values total) if $S_{3\phi base}$ = 100 MVA and $V_{Lbase}$ = 34.5 kV at bus 2.
(b) Draw the positive-sequence equivalent circuit for the given system.
Locate all four buses.
(c) Convert all impedance data provided into per unit, and enter those
values in the circuit in (b).
5.13. A 2400:240-V 1$\phi$ two-winding 100 kVA transformer is to be connected for
2400:2160-V operation as an autotransformer.
(a) Draw a connection diagram.
(b) Compute its kVA rating as an autotransformer.
(c) Suppose the original transformer had a full-load efficiency of 95%. What
is its full-load efficiency as an autotransformer?