When travelers from the USA and Canada visit Europe, they encounter a different power distribution system. Rated voltages in North America are 120 V rms at 60 Hz, while typical rated voltages in Europe are 230 V at 50 Hz. Many travelers carry small step-down transformers so that they can use their appliances in the countries that they are visiting. They tested in Europe a 1000 VA, 230/115 V step-down transformer to determine its excitation branch components, its series impedances, its voltage regulation, and its efficiency. The following test data have been taken from the primary side of the transformer:
Open-circuit test: Voc = 200 V, Ioc = 0.45 A, Poc = 80 W
Short-circuit test: Vsc = 19.1 V, Isc = 8.7 A, Psc = 42.3 W
Answer the following questions based on the test results as shown above in the table:
a. Design the equivalent circuit with internal parameter values of a real transformer with respect to the transformer model referred to its high voltage side. [10 marks]
b. Calculate the full-load voltage regulation and draw the phasor diagram at 0.8 lagging power factor using the exact equation for Vp. [08 marks]
c. What is the efficiency of this transformer at full load with a power factor of 0.8 leading? [07 marks]