Calculate the available fault current for a 3-phase, 208Y/120-volt main distribution panel. The panel is located 20 feet from the transformer and fed by two parallel runs of 500 kcmil copper conductor. The conductor constant "C" value for this conductor is 22,185. The available fault current at the transformer secondary has been calculated at 46,342 amperes.
Da. 15,556 A
Db. 23,107 A
Dc. 39,483 A
Dd. 46,342 A