Two generator supplying a load, Generator 1: 380 V , two-pole, three phase synchronous generator's prime mover has a no-load speed of 3630(r)/(m)in, a full-load speed of 3570 (r)/(m)in, and a slope SP1 of 0.1M(W)/(H)r.
Generator 2 has 380 V , four-pole, three phase sychronous generator's prime mover has a noload speed of 1800(r)/(m)in, a full load speed of 1785(r)/(m)in. and a slope S_(p2) of 0.15 MW/Hz.
The load supplied by the two oenerator constst of 100 kW at 0.85 PF lapoing.
1- Calculate the speed droops of Generator 1 and Generator 2.
2. Find the operating frequency of the power system, and how much power is supplied by each of the two oenerators?
3-0raw the power-frequency or the house dagram of the system?
4. Suppose an additional 60 KW load were attached to this power system. What would the new sylem frequency be, and how much power would G_(1) and G_(2) woply now?
5. Writ the additional load attached (total load of 160 kW ), find the system freesuricy and the generator powers, at the no had fromonicy of G_(2) is increased by 0.514 .