The parallel flow recuperator described in question 4 becomes fouled over a period of time resulting in the gas temperature rising at outlet to 200°C. If the water flow rate is unchanged, calculate the new heat transfer rate, the exit temperature of the water and the fouling factor. (12.34 kW, 22.35°C and 522.6 W/m$^2$ K)